Question #1
- The intake temperature is measured at 25 °C/77 °F and a relative humidity (RH) level of 50%.
- The exhaust temperature is 29 °C/84 °F and 45% RH.
- The raised floor is providing adequate amount of CFM/CMH at a reasonable velocity.
- The pressure under the raised floor is approximately 25 Pa/0.1 inch H20.
Analyze the situation and indicate what the most likely cause is for this server to crash.
- ADust inside the server causing issues with convection-based heat transfer
- BThe exhaust temperature is exceeding the ASHRAE recommended values
- CThe raised floor pressure is too low and/or the raised floor tile % opening is not adequate
- DNo cause could be determined as the CFM/CMH of the air conditioning equipment is not stated
Hi! Do you need help with this question ?
- Why isn't the A the right answer?
- Traducir la pregunta al español
Contributor get free access to an augmented ChatGPT 4 trained with the latest IT Questions.
Question #2
- AA single ToR (Top of Rack) switch is more expensive than an EoR (End of Row) switch.
- BYou need a separate rack to install all your ToR (Top of Rack) switches.
- CThere will be more switches to manage.
- DA ToR (Top of Rack) switch has only optical interfaces.
Hi! Do you need help with this question ?
- Why isn't the A the right answer?
- Traducir la pregunta al español
Contributor get free access to an augmented ChatGPT 4 trained with the latest IT Questions.
Question #3
Taking energy efficiency as the highest priority, which cooling system should you recommend?
- AStandard air conditioning units, as spares might be not readily available
- BAny cooling system can be efficient, because the outside air temperature will not influence the temperature of the air intake of the ICT equipment
- CWaterside economizer
- DAirside economizer
Hi! Do you need help with this question ?
- Why isn't the A the right answer?
- Traducir la pregunta al español
Contributor get free access to an augmented ChatGPT 4 trained with the latest IT Questions.
Question #4
- AWhen the dry bulb’s temperature is at the lowest allowable temperature for IT equipment as per the ASHRAE
- BWhen the dry bulb’s temperature is at the highest allowable temperature for IT equipment as per the ASHRAE
- CWhen the relative humidity is at the best practice value for relative humidity, being 50% RH
- DWhen the relative humidity is 100%
Hi! Do you need help with this question ?
- Why isn't the A the right answer?
- Traducir la pregunta al español
Contributor get free access to an augmented ChatGPT 4 trained with the latest IT Questions.
Question #5
- Unit-A has a Sensible Heat Ratio (SHR) of 0.7.
- Unit-B has a Sensible Heat Ratio (SHR) of 0.9.
From an efficiency point of view, which one should be selected?
- AIt does not matter, as the Sensible Heat Ratio has nothing to do with efficiency.
- BNot relevant, as Sensible Heat Ratio is only specified for air-conditioner equipment to indicate the ratio between intake temperature and exhaust temperature.
- CUnit A
- DUnit B